Product Overview
The Yokogawa AAI143-S50/A4S00 is a 16-channel, isolated analog input module designed for high-precision signal acquisition in industrial automation systems. It accepts 4–20 mA signals, provides HART communication capability, and features high noise imm件y and channel isolation, making it ideal for critical process monitoring.
Applications
-
Process automation in oil & gas, chemical, and power industries
-
SCADA systems
-
Distributed control systems (DCS)
-
Intrinsically safe areas (with isolation barriers)
-
Redundant control environments
Product Advantages
-
16 fully isolated input channels
-
支持s HART communication
-
Fast 10 ms data update rate
-
High input accuracy (±16 µA)
-
Channel-wise 2-wire/4-wire configuration
-
Strong surge resistance with surge-absorbing terminal block
-
Dual-redundant compatibility for reliability
-
Compact form factor suitable for dense installations
Technical Specifications
| Parameter | Specification |
|---|---|
| 型号 | AAI143-S50/A4S00 |
| Number / Channels | 16 isolated input channels |
| Input Signal Range | 4 to 20 mA DC |
| Allowable Input Current | Up to 24 mA |
| Input Resistance (Power ON) | 270–350 Ω (depends on input current) |
| Input Resistance (Power OFF) | ≥ 500 kΩ |
| Accuracy | ±16 µA |
| Data Update Period | 10 ms |
| Transmitter Power Supply | 19.0 V min @ 20 mA / 25.5 V max @ 0 mA |
| Overvoltage Withstand | 1500 V AC (1 min) |
| Power Consumption | 230 mA (5 V DC), 540 mA (24 V DC) |
| HART Communication | 支持ed |
| External Connection | Pressure clamp terminal (A4S00) |
| Operating Temperature | -20°C to +70°C |
| Dimensions (H × W × D) | 130 × 32.8 × 107.5 mm |
| 重量 | 0.3 kg |
FAQ
Q1: What type / signals does the AAI143 module accept?
A1: It accepts 4 to 20 mA DC current signals.
Q2: Is each input channel isolated?
A2: Yes, all 16 channels are electrically isolated.
Q3: Can the module be used in redundant systems?
A3: Yes, it supports dual-redundant configurations.
Q4: Does it support HART communication?
A4: Yes, it supports HART protocol for compatible devices.
Q5: What is the accuracy / the input measurements?
A5: It /fers ±16 µA accuracy.
Q6: What is the input resistance when powered on?
A6: It ranges from 270 Ω to 350 Ω, depending on the current.
Q7: What type / terminal block does /A4S00 represent?
A7: It refers to a pressure clamp terminal block.
Q8: What kind / isolation voltage does the module withstand?
A8: 1500 V AC between system and input for one minute.
Q9: Can this module power 2-wire transmitters?
A9: Yes, it provides 19–25.5 V for 2-wire transmitters.
Q10: Is a Zener barrier allowed for intrinsic safety?
A10: No, use an isolation barrier instead / a Zener barrier.
Related 型号s (Same Series)
| 型号 | Type | Channels | Signal Type | Isolation | 重量 |
|---|---|---|---|---|---|
| AAI141 | Analog Input | 16 | 4–20 mA | No | 0.2 kg |
| AAB141 | Analog Input | 16 | 1–5 V / 4–20 mA | No | 0.3 kg |
| AAI841 | Analog I/O | 8/8 | 4–20 mA | No | 0.3 kg |
| AAI543 | Analog Output | 16 | 4–20 mA | Yes | 0.4 kg |
| AAV144 | Analog Input | 16 | -10 to +10 V | Yes | 0.2 kg |
| AAI135 | Analog Input (Isolated Channels) | 8 | 4–20 mA | Yes | 0.3 kg |
Popular Yokogawa 型号s
| 型号 | Function | Channels | Signal Type | Isolation | 重量 |
|---|---|---|---|---|---|
| AAI143 | Analog Input | 16 | 4–20 mA | Yes | 0.3 kg |
| AAI543 | Analog Output | 16 | 4–20 mA | Yes | 0.4 kg |
| AAI141 | Analog Input | 16 | 4–20 mA | No | 0.2 kg |
| AAI841 | Analog I/O | 8/8 | 4–20 mA | No | 0.3 kg |
| AAV144 | Analog Input | 16 | -10 to +10 V | Yes | 0.2 kg |
| AAT141 | TC/mV Input | 16 | TC/mV | Yes | 0.2 kg |
公司信息
E-mail: [email protected]
Mobile:请通过邮件联系
Whatsapp:请通过邮件联系
Add: 中国福建省厦门市思明区吕岭路2号阿里山大厦,邮编:361006
我们的服务
我们专业提供工业自动化零部件,并附有一年质保。我们的工业自动化零部件销往全球。
我们能提供来自不同国家和制造商的设备及备件,解决您在多处的顾虑或质量问题,并具有极大的价格优势。
欢迎来电咨询更多产品详情。