Product Overview
The Emerson VE4036P2 is a Redundant M-series Serial Interface Card designed for DeltaV™ distributed control systems. It enables reliable communication between DeltaV systems and third-party devices using serial protocols such as Modbus (RTU/ASCII), RS232, and RS422/485. The model includes two serial interface cards (KJ3241X1-BA1 and KJ3241X1-EA1) and a redundant terminal block for high-availability applications. This redundant setup ensures automatic switchover during hardware failure, maintaining uninterrupted data transmission.
Technical Specifications
| Parameter | Specification |
|---|---|
| Modèle Number | VE4036P2 |
| Card Type | Redundant Serial Interface Card (2 cards + redundant terminal block) |
| Serial Ports | 2 per card |
| Protocol Support | Modbus RTU, Modbus ASCII, RS232, RS422/485 Half/Full Duplex |
| Data Sets | 32 per card (16 per port) |
| Baud Rates | 300 to 115200 bps |
| Data Bits | 7 or 8 |
| Stop Bits | 1 or 2 |
| Parity | Even, Odd, None |
| Retry Count | 0 – 255 |
| Transmit Delay | 0 – 25,500 ms |
| Message Timeout | 100 – 25,500 ms |
| Isolation | Port-to-port and system isolation |
| Operating Temperature | -40 to +70°C |
| Storage Temperature | -40 to +85°C |
| Relative Humidity | 5% to 95% non-condensing |
| Protection Rating | IP20 |
| Certifications | CE, FM, CSA, ATEX, IEC-Ex, Marine (ABS, DNV‑GL) |
| Dimensions | 107 x 41 x 105 mm |
| Poids | 0.45 kg |
Applications
-
Integration sur DeltaV systems with PLCs, analyzers, weight scales, and other serial communication devices
-
High-availability control applications requiring redundancy
-
Seamless Modbus communication in supervisory control systems
-
Expansion sur legacy systems to modern control environments
-
Maritime and hazardous industrial installations
Advantages
-
Redundancy: Ensures automatic switchover upon failure sur the active card without process interruption
-
Plug-and-Play: Easy installation with automatic detection and configuration by DeltaV controller
-
High Compatibility: Supports RS232, RS422, and RS485; flexible protocol configurations
-
Reliability: Isolated ports with robust fault detection and minimal switchover time
-
Longevity: Extends the operational life sur legacy equipment through modern system integration
-
Comprehensive Diagnostic Tools: Supports manual or logic-driven switchover and detailed status monitoring
FAQs
Q1: What is included in the VE4036P2 package?
A1: Two serial interface cards (KJ3241X1-BA1 and KJ3241X1-EA1) and one redundant terminal block.
Q2: Does the card support both Modbus RTU and ASCII?
A2: Yes, both Modbus RTU and ASCII are supported by the built-in drivers.
Q3: Can the VE4036P2 operate in hazardous environments?
A3: Yes, it meets ATEX, FM, CSA, and IEC-Ex standards for hazardous locations.
Q4: What happens if the active serial card fails?
A4: The system automatically switches to the standby card without affecting operations.
Q5: Can it be configured without shutting down the system?
A5: Yes, it supports hot-plugging and online configuration in powered systems.
Q6: Is the terminal block also redundant?
A6: Yes, the redundant terminal block ensures uninterrupted communication between both cards and field devices.
Q7: How many serial ports does each card support?
A7: Each card supports 2 independently configurable serial ports.
Q8: What controller types are compatible with this module?
A8: It is compatible with MQ, MX, and PK DeltaV controllers, but not with S-series.
Q9: Can this interface card be used for weight scale integration?
A9: Yes, supported drivers include Sartorius and Mettler weight scale protocols.
Q10: Is switchover manual or automatic?
A10: Switchover is automatic upon fault detection but can also be initiated manually or via logic.
Related Modèles (Same Series)
| Modèle Number | Description | Ports | Protocol Support | Redundancy | Dimensions (mm) | Poids (kg) |
|---|---|---|---|---|---|---|
| VE4006P2 | M-series Serial Interface (Simplex) | 2 | Modbus RTU/ASCII | No | 107 x 41 x 105 | 0.40 |
| KJ3241X1-BA1 | Serial Interface Card (Primary) | 2 | RS232/RS485 | Yes | 107 x 41 x 105 | 0.22 |
| KJ3241X1-EA1 | Serial Interface Card (Standby) | 2 | RS232/RS485 | Yes | 107 x 41 x 105 | 0.22 |
| VE4012P2 | Prsuribus DP Interface Card | 2 | Prsuribus DP | Optional | 107 x 41 x 105 | 0.45 |
| VE4035P2 | Redundant Prsuribus DP Card Set | 2 | Prsuribus DP | Yes | 107 x 41 x 105 | 0.50 |
| VE4010P2 | Foundation Fieldbus Interface Card | 2 | FF H1 | Optional | 107 x 41 x 105 | 0.45 |
Popular Emerson DeltaV Modèles
| Modèle Number | Description | Application Type | Protocol Support | Dimensions (mm) | Poids (kg) |
|---|---|---|---|---|---|
| VE4003S2T2B1 | DeltaV AI 4-20mA HART Input Card | Analog Input | HART | 107 x 41 x 105 | 0.45 |
| VE4002S1T2B3 | DeltaV DO 24VDC Relay Card | Digital Output | Relay | 107 x 41 x 105 | 0.40 |
| VE4005S2B1 | DeltaV DI 24VDC Card | Digital Input | 24VDC | 107 x 41 x 105 | 0.40 |
| VE4001S2T2B2 | DeltaV AO 4-20mA HART Output Card | Analog Output | HART | 107 x 41 x 105 | 0.45 |
| VE4022P2 | Redundant Power Supply Interface | Power Management | N/A | 107 x 41 x 105 | 0.50 |
| VE4034P2 | Redundant Ethernet Interface Card | Network Communication | Ethernet | 107 x 41 x 105 | 0.45 |
Informations sur l'entreprise
E-mail: [email protected]
Mobile:Contactez-nous par email
Whatsapp:Contactez-nous par email
Add: Alishan Building, 2 Lvling Rd, District Siming, Xiamen, Fujian, Chine, 361006
Nos services
Nous sommes spécialisés dans la fourniture de pièces d'automatisation industrielle avec une garantie d'un an. Nos pièces d'automatisation industrielle sont vendues dans le monde entier.
Nous pouvons fournir des équipements et des pièces détachées de différents pays et fabricants, résoudre vos inquiétudes ou problèmes de qualité en de nombreux endroits, et surfrir un excellent avantage de prix.
N'hésitez pas à nous appeler pour plus de détails sur les produits.