製品紹介
The Yokogawa SAI143-S63/A4S00 Analog Input Module is designed for industrial process automation systems. It provides precise, reliable 4–20 mA signal acquisition with high channel isolation, suitable for integration into both standard and safety instrumented systems. Its compact design ensures easy installation in distributed control systems (DCS) and safety control architectures.
Technical Specifications
| Parameter | Specification |
|---|---|
| Input Channels | 16 independent channels |
| Input Signal Range | 4–20 mA DC |
| Permissible Input Range | 0–25 mA DC |
| Accuracy | ±16 µA (1–23 mA range) |
| Input Impedance | 250 Ω (Power ON), ≥500 kΩ (Power OFF) |
| Data Update Frequency | 40 ms |
| Temperature Drift | ±16 µA / 10°C |
| Transmitter Power Supply | 16.15–26.4 V DC, 25 mA max |
| Dual Redundancy | サポートed |
| Communication Protocol | HART |
| Operating Temperature | -20°C to 70°C |
| Mounting Options | Clamp terminals, MIL connector, or dedicated cables |
| Dimensions | 130 × 107.5 × 32.8 mm |
| 重量 | 0.39 kg |
Applications
-
Process signal monitoring and control in DCS.
-
Integration in Safety Instrumented Systems (SIS).
-
Field instrumentation data acquisition.
-
Industrial automation requiring high channel isolation.
Advantages
-
High-precision analog signal acquisition.
-
Individual channel isolation minimizes cross-talk.
-
サポートs dual-redundant configurations for enhanced reliability.
-
Compact size allows easy integration into control cabinets.
-
HART communication support enables diagnostics and configuration.
-
Robust performance under wide temperature conditions.
FAQ
1. What signal types are supported?
The module supports 4–20 mA DC input signals.
2. Can it handle over-range signals?
Yes, it supports up to 25 mA input without damage.
3. How fast is the data update?
The module updates data every 40 ms.
4. Is HART communication supported?
Yes, HART protocol is supported for device diagnostics.
5. Can it be used in redundant systems?
Yes, dual-redundant configurations are supported.
6. What is the operational temperature range?
It operates from -20°C to 70°C.
7. How many channels are there?
There are 16 independent analog input channels.
8. What is the power supply requirement?
16.15–26.4 V DC with a maximum current / 25 mA.
9. What is the module’s accuracy?
Accuracy is ±16 µA within the 1–23 mA input range.
10. What mounting options are available?
Clamp terminals, MIL connector cables, or dedicated signal cables can be used.
Related Series / モデルs
| モデル | Channels | Input Type | Dimensions (mm) | 重量 (kg) |
|---|---|---|---|---|
| SAI143-S63/A4S01 | 16 | 4–20 mA | 130 × 107.5 × 32.8 | 0.39 |
| SAI143-S53/A4S00 | 16 | 4–20 mA | 130 × 107.5 × 32.8 | 0.39 |
| SAI143-H63/A4S00 | 16 | 4–20 mA | 130 × 107.5 × 32.8 | 0.39 |
| SAI143-S63/B4S00 | 16 | 4–20 mA | 130 × 107.5 × 32.8 | 0.39 |
| SAI143-S63/A4T00 | 16 | 4–20 mA | 130 × 107.5 × 32.8 | 0.39 |
| SAI143-S63/C4S00 | 16 | 4–20 mA | 130 × 107.5 × 32.8 | 0.39 |
Popular Yokogawa モデルs
| モデル | Channels | Input Type | Dimensions (mm) | 重量 (kg) |
|---|---|---|---|---|
| SAI143-S33 | 16 | 4–20 mA | 130 × 107.5 × 32.8 | 0.39 |
| SAI143-H33 | 16 | 4–20 mA | 130 × 107.5 × 32.8 | 0.39 |
| SAI143-S63 | 16 | 4–20 mA | 130 × 107.5 × 32.8 | 0.39 |
| SAI143-S53 | 16 | 4–20 mA | 130 × 107.5 × 32.8 | 0.39 |
| SAI143-A63 | 16 | 4–20 mA | 130 × 107.5 × 32.8 | 0.39 |
| SAI143-B63 | 16 | 4–20 mA | 130 × 107.5 × 32.8 | 0.39 |
会社情報
E-mail: [email protected]
Mobile:メールでのお問い合わせ
Whatsapp:メールでのお問い合わせ
Add: 中国福建省廈門市思明区呂嶺路2号 阿里山ビル 〒361006
サービス内容
当社は産業用オートメーション部品の供給を専門としており、1年間の保証を提供しております。当社の産業用オートメーション部品は世界中に販売されています。
当社は様々な国やメーカーの機器及びスペアパーツを提供し、複数拠点でのご不安や品質問題を解消するとともに、大きな価格メリットを実現しております。
製品詳細については、お気軽にお電話にてお問い合わせください。