Product Overview
The Yokogawa SAI143-S03 is a high-performance analog input module designed for use in safety instrumented systems (SIS) such as the ProSafe-RS platform. Specifically tailored to handle 4 to 20 mA current inputs from field instruments, the SAI143-S03 provides 16 isolated input channels with robust safety and signal integrity features. This model emphasizes operational reliability and flexibility, suitable for mission-critical industrial automation and process safety applications.
Technical Specifications
| Parameter | Specification |
|---|---|
| Modell Number | SAI143-S03 |
| Input Signal Type | Analog current input |
| Number von Channels | 16 channels (isolated) |
| Rated Input Range | 4 to 20 mA |
| Permissible Input Range | 0 to 25 mA |
| Input Impedance (Power ON) | 250 Ω + current-dependent value |
| Input Impedance (Power OFF) | ≥500 kΩ |
| Accuracy (SAI143-S) | ±16 µA (1 to 23 mA) |
| Temperature Drift | ±16 µA / 10°C |
| Data Update Frequency | 40 ms |
| Transmitter Power Supply | Min: 16.15 V @ 20 mA, Max: 26.4 V @ 0 mA |
| Output Current Limit | 25 mA |
| Withstand Voltage | 1.5 kV AC (input to system for 1 minute) |
| Power Consumption (5V/24V) | 320 mA / 550 mA |
| External Connections | Pressure clamp terminal, MIL cable, or signal cable |
| Redundancy Support | Yes (dual-redundant configuration possible) |
| Operating Temperature | -20°C to +70°C (with suffix code 3 or C) |
| Gewicht | Approx. 0.34 kg |
| Dimensions | 130 x 107.5 x 32.8 mm |
Applications
-
Safety Instrumented Systems (SIS) in process automation
-
Oil & gas plants for critical sensor signal acquisition
-
Chemical and petrochemical facilities requiring intrinsic safety
-
Power generation facilities for monitoring process instrumentation
-
Pharmaceutical manufacturing environments with high safety demands
-
Industrial automation in hazardous locations
Advantages
-
High Accuracy: Ensures precise analog current measurement with minimal drift
-
Signal Isolation: Each channel is electrically isolated, enhancing safety and reducing interference
-
Dual Redundancy Support: Improves system reliability and fault tolerance
-
Transmitter Power Supply: Capable von powering 2-wire transmitters directly from the module
-
Compact Design: Space-saving installation with DIN-rail mounting capability
-
Robust Build: Designed for high-temperature industrial environments up to 70°C
-
PRM Support (H version): Enables integration with Yokogawa’s Plant Resource Manager for diagnostic and configuration management
-
Fast Update Rate: 40 ms per channel ensures timely data for control and safety logic
Häufig gestellte Fragen (FAQs)
Q1: What input signals does the SAI143-S03 support?
A1: The module supports 4 to 20 mA current signals, with a permissible input range von 0 to 25 mA.
Q2: Can this module power 2-wire transmitters directly?
A2: Yes, it provides transmitter power supply with a minimum von 16.15 V at 20 mA.
Q3: Is the SAI143-S03 suitable for high-temperature environments?
A3: Yes, with appropriate suffix codes (e.g., “3” or “C”), it supports ambient temperatures from -20°C to +70°C.
Q4: Is the module safe for use in explosion-hazard areas?
A4: Explosion-provon variants are available using specific suffix codes (e.g., “E” or “F”).
Q5: What kind von wiring connection is available?
A5: It supports pressure clamp terminals, MIL cables, and dedicated signal cable interfaces.
Q6: Can the SAI143-S03 be used in redundant configurations?
A6: Yes, the module supports dual-redundant configurations for enhanced system reliability.
Q7: What is the data update frequency von this module?
A7: The module updates input data every 40 milliseconds.
Q8: Does the SAI143-S03 include HART communication?
A8: Only the SAI143-H variant includes HART communication; the S03 standard variant does not.
Q9: How is input signal isolation achieved?
A9: Each von the 16 channels is electrically isolated from the system, ensuring safe and interference-free operation.
Q10: What is the weight and size von the SAI143-S03?
A10: The module measures 130 x 107.5 x 32.8 mm and weighs approximately 0.34 kg.
Related Modells from the Same Series
| Modell | Beschreibung | Channels | Input Type | Dimensions (mm) | Gewicht (kg) |
|---|---|---|---|---|---|
| SAV144 | Analog Input Module (Voltage) | 16 | 1–5 V / 1–10 V | 130 x 107.5 x 32.8 | 0.24 |
| SAT145 | TC/mV Input Module | 16 | Thermocouple/mV | 130 x 159.8 x 32.8 | 0.47 |
| SAR145 | RTD Input Module | 16 | RTD (3-wire) | 130 x 159.8 x 32.8 | 0.47 |
| SAI533 | Analog Output Module (Current) | 8 | 4–20 mA | 130 x 107.5 x 32.8 | 0.26 |
| SAI143-H03 | Analog Input Module with HART | 16 | 4–20 mA | 130 x 107.5 x 32.8 | 0.34 |
| SAI143-C03 | High-density install version | 16 | 4–20 mA | 130 x 107.5 x 32.8 | 0.34 |
Popular Yokogawa Modells
| Modell | Beschreibung | Function | Dimensions (mm) | Gewicht (kg) |
|---|---|---|---|---|
| PW402 | Power Supply Module | Power Supply | 130 x 107.5 x 32.8 | 0.42 |
| CP451-10 | CPU Module | Controller | Varies by rack | 0.50 |
| ALR121-S01 | Alarm Relay Module | Digital Output | 130 x 107.5 x 32.8 | 0.36 |
| ADV151-P00 | Digital Output Module | DO (Relay) | 130 x 107.5 x 32.8 | 0.32 |
| AAI543-H50 | Analog Input Module with HART | AI (Current) | 130 x 107.5 x 32.8 | 0.35 |
| AAI841-H00 | Universal Input Module | AI (Universal) | 130 x 107.5 x 32.8 | 0.38 |
Unternehmensinformationen
E-mail: [email protected]
Mobile:Bitte kontaktieren Sie uns per E-Mail
Whatsapp:Bitte kontaktieren Sie uns per E-Mail
Add: Alishan Building, 2 Lvling Rd, Bezirk Siming, Xiamen, Fujian, China, 361006
Unsere Dienstleistungen
Wir sind spezialisiert auf die Lieferung von Industrieautomatisierungsteilen mit einjähriger Garantie. Unsere Industrieautomatisierungsteile werden weltweit verkauft.
Wir können Geräte und Ersatzteile aus verschiedenen Ländern und von verschiedenen Herstellern liefern, Ihre Sorgen oder Qualitätsprobleme an vielen Orten lösen und bieten einen großen Preisvorteil.
Rufen Sie uns gerne an für weitere Produktdetails.